Project Case · Data Centres and Industrial Plant
Generator Connection Bar Insulation After a Bridging Fault
Retrofitting insulated bar and joint covers on a live critical facility
Client Background
A critical facility suffered a phase to phase fault on the connection bar between a standby generator and its MV switchgear. Investigation found the fault was initiated by an animal bridging two bare bars inside the enclosure.
Project Challenge
Insulate the connection bar system on a facility that cannot take an extended outage, using a method that also handles the bolted terminations at each end.
Customer Pain Points
- Bare bar inside an enclosure that could not be made animal proof
- A critical facility with a very short permitted outage
- Bolted terminations at the generator and switchgear ends that a tube cannot cover
- The facility's maintenance policy requiring joint inspection to remain possible
Our Solution
S1 busbar insulation tube on the straight bar sections and S1-B molded covers on the bolted terminations at each end. The S1 family carries UL 224 recognition under file E341796 which satisfied the facility's equipment approval policy.
Manufacturing Process
Tube supplied cut to the measured bar lengths. Covers tooled from a dimensioned survey of the actual terminations carried out during a planned maintenance window.
Supply Chain Coordination
Survey to first article to production ran inside the facility's planned maintenance cycle so the retrofit needed only one short outage.
Quality Control
Per lot testing plus a fit check of the first article covers on the actual terminations before production.
Final Result
The retrofit was completed inside a single short outage. Both generator sets have since been insulated to the same standard and the facility added insulated bar to its standard for all new MV connections.
Customer Benefit
A recurring failure mode eliminated on a facility that could not afford the outage a full switchboard rebuild would have needed.
Products
Products Supplied on This Project
S1 Busbar Tube
The general purpose busbar insulation family covering 1 kV to 35 kV with UL 224 recognition under file E341796
VIEW DETAILSS1-B Lap Joint Cover
Molded clip open covers that insulate bolted busbar joints and still allow inspection without damaging the connection
VIEW DETAILSS1(n)-10 Busbar HF 24 kV
Halogen free red tubing that insulates round and rectangular copper or aluminium busbar inside 6 to 24 kV switchgear
VIEW DETAILSS1-A Overhead Line Cover
A wrap around insulating cover with a built in creepage device that clips onto a live route conductor without disconnection
VIEW DETAILSFAQ
Questions About This Project
Can bar be insulated without removing it
What does UL 224 recognition mean
How are covers tooled for existing terminations
Is insulated bar now standard practice
Still need an answer ask our engineers on WhatsApp
More Cases
Other Projects
15 kV Feeder Refurbishment for a Distribution Utility in Southeast Asia
820 terminations and 140 joints delivered against a 14 week outage programme
READ CASE →Retrofitting Creepage on Flashover Prone Outdoor Terminations
Rain sheds fitted to 96 existing 33 kV terminations without rebuilding any of them
READ CASE →Accessory Package for a 350 MW Solar Collector Circuit
Take off from a single line diagram consolidated 14 part numbers down to 5
READ CASE →Discuss a Project Like This One
Tell us the voltage class the quantity and the programme. We will tell you what is realistic before you commit.