FA Series EN733 Horizontal Centrifugal Pump
BS EN733 / DIN24255 end-suction pump, 2 to 1100 m³/h and head to 152 m, for building services fire and irrigation
View specificationsTwo names, one set of dimensions. Why both still appear on specifications and what they fix on an end-suction pump.
DIN24255 was the German standard for end-suction centrifugal pumps. BS EN733 is the European standard that replaced it. The dimensions carried across, which is why datasheets — including the Flowsteer FA series — quote both.
For a buyer, the practical consequence is simple: a pump built to EN733 lands on a baseplate laid out for DIN24255, and the reverse.

EN733 applies to end-suction centrifugal pumps with a rated pressure of 10 bar. It fixes the nominal duty points, the flange sizes and positions, the shaft centreline height and the foot mounting dimensions.
Sizes run from DN32 upward. The Flowsteer FA series covers DN32 to DN250 within that framework.
Like the ANSI and ISO standards, it fixes geometry rather than performance.
Specifications written before the European standard came into force still call out DIN24255, and those specifications get reused for decades.
Manufacturers quote both to make clear that a pump satisfies either reference. The Flowsteer FA series datasheet states 'Design: BS EN733/DIN24255' for exactly that reason.
If a specification quotes only DIN24255, an EN733 pump meets it dimensionally.
The FA series is supplied with DIN2501 flanges as standard. That is the natural pairing for an EN733 pump on European pipework.
ANSI B16.5 150lb flanges are available as an option, which is how the series handles projects where the pipe class is American but the pump layout is European.
Decide this at enquiry stage. Changing the flange standard after manufacture means new casings, not new gaskets.
EN733 does not set the performance envelope; the manufacturer does. The FA series publishes flow from 2 to 1100 m³/h and head from 2 to 152 m across its size range.
Speed matters as much as size: 1450 to 2900 rpm at 50 Hz, 1750 to 3500 rpm at 60 Hz. The same casing on a different supply frequency is a different pump in practice.
Temperature runs -10 °C to 105 °C and working pressure is 1.2 MPa standard, 1.6 MPa on request.
Building services — chilled water, condenser water and heating circulation.
Fire protection, where the 1.6 MPa option is often the deciding factor.
Municipal water supply, distribution and boosting.
Irrigation, where flow matters more than head.

BS EN733 / DIN24255 end-suction pump, 2 to 1100 m³/h and head to 152 m, for building services fire and irrigation
View specifications
B73.1 is a dimensional standard, not a performance standard. Knowing the difference is what makes a replacement pump drop straight onto an existing baseplate.
Read more
One standard says where the holes go. The other says how long the pump should last. Specifications usually need both.
Read more
A published envelope such as 2 to 1100 m3/h is a range of sizes, not the capability of any one pump. Here is how to get from it to a selection.
Read moreFor the purposes of mounting and connecting a pump, yes. EN733 replaced DIN24255 and carried the dimensions across.
The standard applies to pumps with a rated pressure of 10 bar. The Flowsteer FA series publishes a working pressure of 1.2 MPa as standard and 1.6 MPa on request.
Yes. The FA series offers DIN2501 as standard and ANSI B16.5 150lb as an option.
No. It fixes dimensions. The FA series publishes its own envelope of 2 to 1100 m³/h and 2 to 152 m.
Send the pump details and the duty point and we will tell you what this means for your installation rather than in general.