Qianwei Current Transformer Co., Ltd.  ·  Liushi, Zhejiang, China+86-577-62700712[email protected]WhatsApp +86 186 5836 9816
QIANWEI® Current Transformer
  1. Home
  2. Products
  3. Split Core And Clamp On CTs
  4. UK Ring Split Core Current Transformer
UK Ring Split Core Current Transformer
UK series

UK Ring Split Core Current Transformer

A split core with an internal precision resistor across the secondary. The output is a low, safe voltage rather than a current, so an open secondary is no longer a hazard waiting to happen in the panel.

  • Rated input100 A to 1000 A
  • Rated output5 A / 1 A
  • Ratio error≤ ±0.5 %
  • Phase angle≤ ±30 min
  • Frequency50 to 400 Hz
  • Measuring range5 %In to 130 %In
  • Dielectric strength2.5 kV / 1 mA / 1 min
  • CasePA / UL94-V0

Product Overview

The UK series split core current transformer has been specially designed to make installation easy in new or already existing networks. They may be installed without opening any cable or busbar circuit.

An internal precision resistor across the secondary winding of the CT provides a low safe voltage output. It saves time and installation costs.

Application Scenarios

  • Current measurement, monitoring and protection for electrical wiring and equipment
  • Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air conditioning equipment and automation control systems
  • Current, power and energy monitoring devices
  • Relay protection devices

Technical Features

  • Double screw fastening: safe, easy to install, portable
  • Wide inner window allowing clamping of big cables or busbars
  • Wide range of sizes to accommodate all existing installations
  • Internal precision resistor for a low safe voltage output

Specifications

Technique index

Electrical parameterValueMechanical parameterValue
Frequency50 to 400 HzCasePA / UL94-V0
Rated input100 A to 1000 ABobbinPA
Measuring range5 %In to 130 %InCoreSilicon steel
Rated output5 A / 1 AInternal structureEpoxy
Ratio≤ ±0.5 %ConstructionTie
Phase angle≤ ±30 minOperating temperature-25 °C to +75 °C
Dielectric strength2.5 kV / 1 mA / 1 minOperating humidity≤ 85 %
Insulation resistanceDC 500 V / 100 MΩ minOutput connectionTerminal

Burden by ratio and class (VA)

Input / outputClass 0.5Class 1.0Class 3.0
100/5 A1.52.53.75
150/5 A1.52.53.75
200/5 A1.52.55
250/5 A1.52.55
300/5 A2.52.55
400/5 A2.53.755
500/5 A2.53.755
600/5 A2.53.755
800/5 A51015
1000/5 A51015

The same burden ladder applies to the 1 A secondary versions (100/1 A to 1000/1 A).

FAQ

Questions Buyers Ask

What does the internal precision resistor do?

It burdens the secondary permanently, so the transformer presents a low safe voltage instead of a current source. That removes the open secondary hazard and lets the output feed a voltage input directly.

Does the UK series work at 400 Hz?

Yes, the specified frequency range is 50 to 400 Hz, which covers aviation and variable frequency ground power applications.

How is it fixed?

Double screw fastening around the conductor.

Related Products

Compare With These Frames

Get UK Ring Split Core Current Transformer Quoted Today

Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.

WhatsAppEmail