Two numbers on a rating plate decide whether a reading can be billed. Here is what they guarantee, and where the guarantee stops.

A measuring class such as 0.5 limits the ratio error at rated current. The class is a promise about accuracy near the top of the range, and the error is allowed to grow as the current falls. Standard measuring classes across this range are 3, 1, 0.5, 0.5S, 0.2 and 0.2S.
A feeder that idles overnight and peaks in the morning spends most of its life at a small fraction of rated current. An ordinary Class 0.5 transformer only has to hold 0.75 % error at 5 % of rated current. A Class 0.5S has to hold its error down at 1 % of rated current, which is why revenue metering specifications call for the S classes.
A protection class is written differently: 5P20 means 5 % composite error at an accuracy limit factor of 20 times rated primary current. The design goal is the opposite of a measuring core. A measuring core is meant to saturate above rated current to protect the instrument; a protection core is meant to stay linear so the relay can see the fault.
Every accuracy class is declared against a rated burden. Change the burden and the class no longer applies, which is why burden and class have to be specified together.