D364 Three Phase Current Transformer
Type Three phase current transformer
Position in range Low cost three phase option
Three cores in one moulded body that sits directly on top of the breaker. One part number instead of three, one mounting operation instead of three, and the panel gets its space back.
The three in one current transformer is designed to be used at the top of the MCCB. The current transformer saves a lot of space and time.
The three phase (M3N1) current transformer is suitable for primary ratings from 100 A to 1200 A with 5 A secondary. It allows installation directly on top of moulded case circuit breakers for greater speed of installation and optimisation of space. Applicable MCCBs include the ABB Isomax series, Merlin Gerin NS series and Changshu CM1 series.
| Model | Ratio | Class | Burden |
|---|---|---|---|
| TASN-25-60/5 | 60/5 A | Class 1 | 1 VA |
| TASN-25-100/5 | 100/5 A | Class 1 | 1.5 VA |
| TASN-25-125/5 | 125/5 A | Class 1 | 1.5 VA |
| TASN-25-150/5 | 150/5 A | Class 1 | 1.5 VA |
| TASN-25-160/5 | 160/5 A | Class 1 | 1.5 VA |
| TASN-35-100/5 | 100/5 A | Class 1 | 1.5 VA |
| TASN-35-125/5 | 125/5 A | Class 1 | 1.5 VA |
| TASN-35-150/5 | 150/5 A | Class 1 | 1.5 VA |
| TASN-35-160/5 | 160/5 A | Class 1 | 1.5 VA |
| TASN-35-200/5 | 200/5 A | Class 1 | 1.5 VA |
| TASN-35-250/5 | 250/5 A | Class 1 | 1.5 VA |
| TASN-45-250/5 | 250/5 A | Class 1 | 1.5 VA |
| TASN-45-300/5 | 300/5 A | Class 1 | 2.5 VA |
| TASN-45-400/5 | 400/5 A | Class 1 | 2.5 VA |
| TASN-45-500/5 | 500/5 A | Class 1 | 2.5 VA |
| TASN-45-600/5 | 600/5 A | Class 1 | 2.5 VA |
| TASN-45-630/5 | 630/5 A | Class 1 | 2.5 VA |
| Parameter | Value |
|---|---|
| System voltage | 720 V, 50-60 Hz |
| Test voltage | 3 kV for 1 minute |
| Thermal short circuit current (Ith) | 60 × In |
| Dynamic short circuit current (Idyn) | 2.55 × Ith |
| Housing | Flame retardant polycarbonate UL94 V-0 |
| International standards | IEC/EN 60044-1 |
| Mounting | DIN rail, busbar or base |
| Apertures | 15 × 25 mm, 21 × 25 mm, 31 × 31 mm |





The published applicable list is the ABB Isomax series, the Merlin Gerin NS series and the Changshu CM1 series. Send the breaker model and frame size and an engineer will confirm the aperture and centres.
The aperture and hole centres, and therefore the current range: 25 covers 60 A to 160 A, 35 covers 100 A to 250 A and 45 covers 250 A to 630 A.
Yes, DIN rail, busbar and base mounting are all supported.
The D364 three phase current transformer is the low cost three phase body in the range.
Type Three phase current transformer
Position in range Low cost three phase option
Protection classes 5P5, 5P10, 5P20, 10P5, 10P10, 10P20
Frames PR30, PR70, PR85, PR170
Primary current 5 A to 5000 A
Secondary current 5 A, 1 A, 0.5 A, 0.25 A, 0.1 A
Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.