- Home
- Products
- Moulded Case And Busbar CTs
- DSC Current Transformer
DSC series
DSC Current Transformer
The long running seven frame busbar body. Nothing decorative on it: busbar mounting, a full 5 A to 3000 A ladder and the same 3 kV test voltage as the rest of the range.
- Primary current5 A to 3000 A
- Secondary current5 A / 1 A
- Rated frequency50 / 60 Hz
- Rated test voltage3 kV AC (1 min)
- Rated voltage Um0.72 kV AC
- Continuous overload Id1.2 In
- Operating temperature-10 °C to 50 °C
- MountingBusbar
Product Overview
An established range of seven frames of plastic case current transformer, offered as the low cost option in the catalogue for Asian, South African and Russian markets.
Application Scenarios
- Current measurement, monitoring and protection for electrical wiring and equipment
- Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air conditioning equipment and automation control systems
- Current, power and energy monitoring devices
- Relay protection devices
Technical Features
- Busbar mounting
- Seven frames covering the common ratios
- Primary current from 5 A to 3000 A
Specifications
Specification
| Parameter | Value |
|---|---|
| Rated frequency | 50 / 60 Hz |
| Rated test voltage | 3 kV AC (1 min) |
| Rated short time thermal current (Ith) | 60 In |
| Rated dynamic current (Idyn) | 2.5 Ith |
| Rated voltage (Um) | 0.72 kV AC |
| Continuous overload (Id) | 1.2 In |
| Operating temperature | -10 °C to 50 °C |
| Housing self extinguishing class | V0 |
| Safety factor | FS 5 |
| Secondary current | 5 A / 1 A |
FAQ
Questions Buyers Ask
Where does DSC sit against MBO and ABO?
DSC is the established economy body for busbar mounting. MBO adds the Euro style case and reinforced terminals; ABO adds high accuracy up to Class 0.2S and sealing.
Is a DIN rail version available?
The DSC body is specified for busbar mounting. For DIN rail duty use the MES or DM families.
Related Products
Compare With These Frames
Get DSC Current Transformer Quoted Today
Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.