A range of ten compact plastic case frames. Much smaller in volume than a general purpose model, with an integral hinged plate terminal cover and DIN rail mounting, so the series fits panels where space has already run out.
- Primary current5 A to 3000 A
- Secondary current5 A / 1 A
- Rated frequency50 / 60 Hz
- Rated test voltage3 kV AC, 1 min
- Rated voltage Um0.72 kV AC
- Short time thermal currentIth = 60 In
- Dynamic current Idyn2.5 Ith
- Operating temperature-10 °C to 50 °C
Product Overview
A range of ten frames of compact design plastic case current transformer. Its volume is much smaller than the general model. An integral hinged plate terminal cover and DIN rail mounting make this series match the requirements of space limited panels.
Published frames: MES-62/B, MES-62/20, MES-62/30, MES-62/40, MES-80/30, MES-80/40, MES-80/50, MES-100/60, MES-100/80 and MES-145/100.
Application Scenarios
- Current measurement, monitoring and protection for electrical wiring and equipment
- Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air conditioning equipment and automation control systems
- Current, power and energy monitoring devices
- Relay protection devices
Technical Features
- Three built in fixing methods: side base, DIN rail and busbar mounting
- Built in hinged terminal cover
- Compact design, ten frames in the family
- Primary current from 5 A to 3000 A
Specifications
Specification
| Parameter | Value |
|---|---|
| Rated frequency | 50 / 60 Hz |
| Rated test voltage | 3 kV AC (1 min) |
| Rated short time thermal current (Ith) | 60 In |
| Rated dynamic current (Idyn) | 2.5 Ith |
| Rated voltage (Um) | 0.72 kV AC |
| Continuous overload (Id) | 1.2 In |
| Operating temperature | -10 °C to 50 °C |
| Housing self extinguishing class | V0 |
| Safety factor | FS 5 |
| Secondary current | 5 A / 1 A |
MES Busbar Instrument Current Transformer Gallery




Questions Buyers Ask
What is the difference between this and the MES moulded case series?
This is the window type body: the conductor passes through the aperture and there is no primary terminal. The moulded case MES page covers the same electrical family with the wider frame ladder and full burden table.
Does the window accept a busbar as well as a cable?
Yes. Every frame is dimensioned for both, and the body carries busbar mounting features as one of the three built in fixing methods.
Is 1 A secondary available on every frame?
Yes, 5 A and 1 A secondaries are standard across the series.