Qianwei Current Transformer Co., Ltd.  ·  Liushi, Zhejiang, China+86-577-62700712[email protected]WhatsApp +86 186 5836 9816
QIANWEI® Current Transformer
  1. Home
  2. Products
  3. Flexible Rogowski Coil CTs
  4. Three Phase Rogowski Coil Current Transformer
Three Phase Rogowski Coil Current Transformer
RS 3P series

Three Phase Rogowski Coil Current Transformer

A rope, not a ring. The coil fits panels, wire bundles and irregular bus where a solid or split core simply will not go, and because there is no magnetic core there is no saturation to design around.

  • Input current range0 to 10000 A
  • Output0.333 Vac, 100 mV per 1000 A, or 0 to 5 Vac
  • Bandwidth1 Hz to 1 MHz
  • Accuracy≤ ±1 %
  • Response time< 10 ms
  • Auxiliary power supply6 to 12 VDC
  • Coil length≤ 2 m
  • Operating temperature-20 °C to 55 °C

Product Overview

The flexible Rogowski coil current transformer series is designed for easy integration in a variety of applications and systems. The rope like coil allows it to fit into any constrained spatial configuration ranging from panels, wire bundles or irregular sized bus where a regular solid core CT or split core CT cannot be used.

The split design permits non contact AC current or current pulse measurement without requiring that the primary conductor be taken offline and disconnected for the current sensor installation. This method provides for safe, easy and portable measurement of current.

A current sensor based upon the Rogowski coil principle offers significant advantages over the standard magnetic core current transformer. Specifically, since the sensor does not incorporate a magnetic core, magnetic core saturation is avoided.

Application Scenarios

  • Power quality and harmonic measurement
  • Switchgear retrofit and protection
  • Generator, UPS and large drive monitoring
  • Portable current measurement

Technical Features

  • Fits panels, wire bundles and irregular bus where a rigid core cannot
  • No magnetic core, therefore no saturation
  • Non contact installation without taking the conductor offline
  • LED status indicator

Specifications

Rated performance

ParameterValue
Rated current (rms)10 A to 100 kA
OutputmV without integrator, 0-5 V AC with integrator
Power supply9 V to 24 V
Coil length20 cm to 200 cm
TubeUL material
Wire leadShielded cable
Isolation voltage3500 V
Operating temperature-25 °C to +70 °C
Frequency50 Hz to 60 Hz
Accuracy±1 %

Coil dimensions

Dimension (mm)RS-210RS-350RS-420RS-510RS-600RS-800
A window size ±10 %60103125155180245
B coil outside diameter ±10 %73120141171201266
C Rogowski coil diameter6.588810.510.5
D wire lead diameter444444

Full specification

ParameterValue
Input current range0 to 10000 A
Output0.333 Vac, 100 mV per 1000 A, 0 to 5 Vac
Bandwidth1 Hz to 1 MHz
Accuracy≤ ±1 %
Response time< 10 ms
Auxiliary power supply6 to 12 VDC
Coil length≤ 2 m
Status indicatorLED light
Storage temperature range-40 °C to 70 °C
Operating temperature range-20 °C to 55 °C
Storage humidity range10 % to 90 % without dew
Operating humidity range10 % to 90 % without dew
Real Product Photography

Three Phase Rogowski Coil Current Transformer Gallery

Split core flexible Rogowski coil with high frequency 0-5 V output
Split core flexible Rogowski coil with high frequency 0-5 V output
Three phase 3000 A Rogowski coil set in three colours
Three phase 3000 A Rogowski coil set in three colours
1000 A 0.33 V CE and RoHS approved Rogowski coil
1000 A 0.33 V CE and RoHS approved Rogowski coil
FAQ

Questions Buyers Ask

Why does a Rogowski coil not saturate?

There is no iron in it. Saturation is a property of a magnetic core, and a Rogowski coil is wound on a non magnetic former, so the output stays proportional right through a fault.

Do I need an integrator?

The raw coil output is proportional to the rate of change of current, so it must be integrated to give current. Coils are supplied with mV output for instruments that integrate internally, or with an integrator giving 0-5 V AC or 0.333 V.

How accurate is it?

±1 % with a conductor position sensitivity of ±2 % maximum. Keeping the conductor near the centre of the loop and closing the coil properly is what keeps you at the good end of that range.

Which coil length do I need?

Coils run 20 cm to 200 cm. Pick a length that closes comfortably around the conductor bundle without leaving a large loop of slack.

Related Products

Compare With These Frames

Get Three Phase Rogowski Coil Current Transformer Quoted Today

Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.

WhatsAppEmail