- Home
- Products
- Moulded Case And Busbar CTs
- DX Current Transformer
DX Current Transformer
Double terminal entry is the point of the DX body: short circuit links can be fitted so the measuring instrument is disconnected without damaging the CT, and earthing the secondary is a screwdriver job rather than a rework job.
- Primary current50 A to 1000 A
- Secondary current5 A
- Accuracy class1.0
- Rated voltage660 V
- Rated burden1.5 VA to 10 VA
- FramesDX-20, DX-30, DX-40, DX-20L, DX-30L
Product Overview
The DX range of current transformers has been designed with double terminal entry, which allows short circuit links to be fitted when it is necessary to disconnect the measuring instrument from the transformer without damage to the CT, or for easier termination to ground of the CT.
Application Scenarios
- Current measurement, monitoring and protection for electrical wiring and equipment
- Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air conditioning equipment and automation control systems
- Current, power and energy monitoring devices
- Relay protection devices
Technical Features
- Safe, easy to install and portable
- Wide inner window allowing clamping of big cables or busbars
- Wide range of sizes to accommodate all existing installations
- Double terminal entry for short circuit links and easy earthing
Specifications
Technical data
| Model | Primary / secondary | Busbar hole dimension | Rated burden | Class | Rated voltage |
|---|---|---|---|---|---|
| DX-20 | 50/5 A to 150/5 A | 20 mm | 1.5 to 2.5 VA | 1.0 | 660 V |
| DX-30 | 100/5 A to 500/5 A | 30 × 10 mm | 1.5 to 2.5 VA | 1.0 | 660 V |
| DX-40 | 150/5 A to 1000/5 A | 40 × 10 mm | 3 to 10 VA | 1.0 | 660 V |
| DX-20L | 50/5 A to 150/5 A | 20 mm | 1.5 to 2.5 VA | 1.0 | 660 V |
| DX-30L | 100/5 A to 500/5 A | 30 × 10 mm | 1.5 to 2.5 VA | 1.0 | 660 V |
Case dimensions (mm)
| Model | A | B | C | D | E |
|---|---|---|---|---|---|
| DX-20 | 53 | 28 | 57 | 66 | 54 |
| DX-30 | 53 | 28 | 57 | 66 | 54 |
| DX-40 | 71 | 45 | 73 | 81 | 65 |
| DX-20L | 53 | 28 | 57 | 66 | 54 |
| DX-30L | 53 | 28 | 57 | 66 | 54 |
Questions Buyers Ask
Why does double terminal entry matter?
An open secondary on a live current transformer is dangerous. With a second terminal entry a short circuit link stays fitted while the instrument is swapped, so the secondary is never open circuit and the core is never damaged.
Which DX frame matches a 30 × 10 mm busbar?
DX-30 and DX-30L both take a 30 × 10 mm busbar and cover 100/5 A to 500/5 A.
What does the L suffix mean?
The L frames share the electrical rating and case dimensions of the standard frame; they are a body variant. Confirm the exact variant with an engineer before ordering.
Compare With These Frames
Read Before You Specify
How To Calculate Current Transformer Burden
Burden is the single specification most often got wrong, and it is the one that quietly pushes a Class 0.5 transformer outside Class 0.5.
Installation GuideCurrent Transformer Installation Guide
Most current transformer failures are installation failures. Five habits prevent almost all of them.
Get DX Current Transformer Quoted Today
Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.