SCT Clamp Split Core Current Transformer
Maximum continuous primary current 5 A to 120 A
Secondary turns 3000, or per customer datasheet

SCT clip on frames sized to the cable, 333 mV output into the logger, fitted circuit by circuit without a shutdown.
Pin type PCB mount cores in Class 0.1 soldered onto the meter board, with the turns ratio and lead length built to your drawing.
AC split cores on the inverter output and a DIN 43703 shunt on the DC string, with the millivolt drop matched to the monitoring input.
Maximum continuous primary current 5 A to 120 A
Secondary turns 3000, or per customer datasheet
Primary current 5 A to 5000 A
Design One button clamp on, open type
Measurement range 1 mA to 1200 A AC
Ratio 1000:1 or 2000:1 (customised)
Primary current 5 A to 5000 A
Secondary current 5 A, 1 A, 0.5 A, 0.25 A, 0.1 A
333 mV is the most common for modern loggers and BMS inputs; 1 A and 5 A remain standard for panel instruments; mA outputs suit PCB and transducer inputs.
For billing, specify a solid core in Class 0.5S or 0.2S. Split cores have a mating face in the magnetic circuit and are normally used for monitoring and sub metering rather than revenue.
Send the meter model and the input specification and an engineer will confirm the ratio, output and burden.
Tell us the application and the ratings. An engineer replies with the frame, the class and the price.