LMZK Epoxy Resin Split Current Transformer
System voltage 10 kV and 35 kV AC
Duty Current measurement and microcomputer protection
A ground fault does not show up on a phase CT until it is large. A zero sequence core sees the vector sum of all three phases, so it catches the leakage current that is on its way to becoming a fault.
The dry type current transformers LXZK0111-80 are cast in epoxy resin insulated with a big surface creepage distance and are excellent in anti pollution and humidity protection.
With a high grade accuracy it is suitable for protection against large short circuit current, with a secondary current output of 1 A or 5 A. The performance of the products meets IEC 60044-1, IEC 61869-2 and ANSI/IEEE C57.13.
| Parameter | Value |
|---|---|
| Standards | IEC 60044; IEC 61869; ANSI/IEEE C57.13 |
| Rated primary current | 50 to 600 A |
| Rated load | ≤ 5 VA |
| Rated frequency | 50 Hz or 60 Hz |
| Rated secondary current | 5 A or 1 A |
| Rated short time thermal current | 40 kA, 1 s |
| Rated dynamic current | 63 kA |
| Rated insulation level | 12 / 42 / 75 kV |
| FS | ≤ 10 |
| Parameter | Value |
|---|---|
| Material | Epoxy resin |
| Weight | 8 kg |
| Operating temperature | -10 °C to +55 °C |
| Daily average temperature | < +40 °C |
| Storage temperature | -40 °C to +70 °C |
| Altitude | < 1000 m |
| Condition | No severely begrimed, erosive or radioactive gas in the air. Permits long term operation under rated current. |



A single core through which all three phase conductors pass. Under healthy conditions the vector sum of the three currents is zero and the secondary sees nothing. When current escapes to earth the sum is no longer zero, and the core produces an output the relay can act on.
The three figures are the rated voltage, the power frequency withstand and the lightning impulse withstand, which together define how much insulation margin the cast resin body has.
Yes, which is what makes it practical on cables that are already terminated.
System voltage 10 kV and 35 kV AC
Duty Current measurement and microcomputer protection
Type Residual current transformer for fire monitoring
Core High magnetic permeability nickel steel or nanocrystalline
Type Outdoor waterproof split core
Installation Clamp on, no circuit interruption
Type Plastic case protection current transformer
Duty Protective relay input
Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.