LXK Zero Sequence Split Core Current Transformer
Rated primary current 50 A to 600 A
Rated secondary current 5 A or 1 A
A phase current transformer sees a ground fault only once it is large. A zero sequence core sees it while it is still milliamps.

Pass all three phases, and the neutral where there is one, through a single core. Under healthy conditions the currents sum to zero and the secondary sees nothing. When current escapes to earth the sum is no longer zero and the core produces an output proportional to the residual current.
The signal being measured is a small imbalance between large currents, so the core needs very high permeability and very low remanence. High magnetic permeability nickel steel and nanocrystalline materials give both. Ordinary silicon steel does not, which is why a standard measuring core makes a poor residual core.
For ground fault protection rather than monitoring, the cast resin zero sequence range is rated 50 A to 600 A primary with a 40 kA one second thermal current, 63 kA dynamic current and a 12/42/75 kV insulation level, to IEC 60044, IEC 61869 and ANSI/IEEE C57.13.
Every live conductor of the circuit, including the neutral, must pass through the core, and the cable screen must be brought back through it if it is earthed at the far end. Miss either and the core will report a fault that is not there.
Rated primary current 50 A to 600 A
Rated secondary current 5 A or 1 A
Type Residual current transformer for fire monitoring
Core High magnetic permeability nickel steel or nanocrystalline
System voltage 10 kV and 35 kV AC
Duty Current measurement and microcomputer protection
Type Plastic case protection current transformer
Duty Protective relay input