How to choose a German pattern current transformer: nine families, each defined by how the primary conductor is presented and what accuracy class the application needs. Reference only.
- CTBUm < 1.0 kV, 6 kV isolation test, -5 °C to +50 °C
- ASR tube30 A to 1000 A, class 0.2 / 0.5s / 0.5 / 1 / 3
- ASK plug in30 A to 8000 A, class 0.2s / 0.2 / 0.5s / 0.5 / 1
- WSK wound1 A to 150 A, class 0.2 / 0.5s / 0.5 / 1
- KBR KBU split core100 A to 5000 A, class 0.5 / 1
- KSU SUSK summation5 A or 1 A primary, up to 8 circuits
- NH fuse rail100 A to 600 A, class 3
- SASK protection50 A to 2000 A, 5P5 / 10P5 / 5P10 / 10P10
- ASRD three phase set3 × 50 A to 3 × 750 A
Product Overview
At the beginning of 2010 MBS AG, 'Sulzbach Messwandler', introduced a new current transformer, type CTB. It incorporates a higher maximum operating voltage (Um < 1.0 kV), an increased isolation test voltage (6 kV Ueff, 1 min, 50 Hz) and an increased ambient temperature range (-5 °C < T < +50 °C). The CTB connection uses a cage clamp. Production follows DIN EN 60044-1, DIN VDE 0414 part 1 and DIN 42600, with UL certification number 20100426-E336996.
Specifications
Family guide
| Family | Primary | Secondary | Accuracy or protection class |
|---|---|---|---|
| ASR tube | 30 A to 1000 A, circular primary conductor | 5 A, 2 A or 1 A | 0.2, 0.5s, 0.5, 1, 3 |
| ASK plug in | 30 A to 8000 A | 5 A, 2 A or 1 A | 0.2s, 0.2, 0.5s, 0.5, 1 |
| WSK wound | 1 A to 150 A, primary winding and terminals | 5 A, 2 A or 1 A | 0.2, 0.5s, 0.5, 1 |
| KBR / KBU split core | 100 A to 5000 A | 5 A, 2 A or 1 A | 0.5, 1 |
| KSU / SUSK summation | 5 A or 1 A, up to 8 circuits | 5 A, 2 A or 1 A | 0.2, 0.5, 1 |
| NH fuse rail | 100 A to 600 A | 5 A or 1 A | 3 |
| SASK protection plug in | 50 A to 2000 A | 5 A, 2 A or 1 A | 5P5, 10P5, 5P10, 10P10 |
| ASRD / ASK(D) / ASKD / WSKD three phase set | 3 × 50 A to 3 × 750 A | 5 A, 2 A or 1 A | 0.2, 0.5s, 0.5, 1 |
European Current Transformer Cross Reference Gallery










Questions Buyers Ask
How do I choose between ASR, ASK and WSK?
By how the primary is presented. ASR takes a round conductor through a tube, ASK plugs onto a busbar, and WSK has its own primary winding for very low primary currents.
What is an NH fuse rail transformer for?
It mounts on the contact rail of a low voltage high performance fuse, with tip sockets for the secondary connection, so metering is added inside the fuse switch itself.
Which QIANWEI parts correspond?
ASK, ASR and KBU frame ladders are published on this site as product pages. For summation, protection and fuse rail duty, ask an engineer.
Compare With These Frames
Get European Current Transformer Cross Reference Quoted Today
Send the ratio, accuracy class, burden and conductor size. An engineer confirms the frame and the price.