Chemical Processing
Chemical process plant runs on modulating control valves, and every one of them needs a clean pneumatic signal derived from the control room. The PT 700 series lists chemical process industry applications directly, and the T1000 pattern is applied to liquid, gas and slurry processing instrumentation.

What Makes This Application Difficult
Air quality varies across the site
Moisture and oil carried into a transducer will change its behaviour before it stops it working.
Ranges are not standard
Dosing and reactor duty throws up spring ranges that a 3-15 psi unit will not stroke fully.
Corrosive atmospheres attack housings
An instrument that is fine in a pump house can fail early in a chemical bay.
Loops need to be documented for audit
Accuracy, linearity and repeatability have to be quotable, not estimated.
How The Range Addresses It
Transducers are supplied against published air quality requirements: instrument quality air, dew point below 35 F, no particle larger than three microns and maximum 1 ppm oil for the T1500, and ISO 8573-1 Class 1,2 for the PT700. Non-standard ranges are covered by the 500X twelve-line table and the 550 coding system, which reaches 0-120 psig. For documented performance the T7800 is specified to ISA S51.1 at 0.25% full scale.
Products For This Industry
Marsh Bellofram Type TransducerT1500 Electro Pneumatic Transducer
Compact force balance transducer, manifold mountable, 3-15 to 6-30 psig
View specifications →
Flowserve Type TransducerPT700 Electro Pneumatic Transducer
Two-wire piezoelectric microvalve transducer, ATEX EEx ia IIC T4, IP66
View specifications →
Controlair Type Transducer550X Electro Pneumatic Transducer
Miniature EAA-550 series electronic pressure regulator, coded ordering
View specifications →
Fairchild Type TransducerT7800 Electro Pneumatic Transducer
Piezoelectric precision transducer, 0.25% full scale accuracy, NEMA 4X and IP65
View specifications →Related OEM cases
Questions From Chemical Processing Buyers
What air quality do the transducers need
Instrument quality air. The T1500 datasheet asks for a dew point below 35 F, no particle larger than three microns and a maximum oil content of 1 ppm. The PT700 asks for air free from oil, dust and moisture to ISO 8573-1 Class 1,2.
We need an output range that is not 3-15 psi
The 500X table lists twelve current-input ranges from 3-9 psi to 3-120 psi, and the 550 coding system adds zero-based 0-30, 0-60 and 0-120 psig outputs.
Can you give us accuracy figures for a tender
Yes. The T7800 is specified at 0.25% full scale guaranteed and 0.15% typical to ISA S51.1, and the PT700 at linearity below 1% with repeatability below 0.2%.
Get A Recommendation For Your Chemical Loop
Describe the loop, the actuator and the area classification, and we will name the models that fit and the ones that do not.