Wenzhou EAA Electric Co., Ltd — I/P and E/P Transducers Built To Drop Into Imported Instrument LoopsYueqing City, Wenzhou, Zhejiang, ChinaTel +86 577 65165096[email protected]
Request A Quote
7 models

Fairchild Type Transducer

Seven models across two families. The T6000 is the modular instrument that installs seven different ways from one basic unit. The T7800 is the piezoelectric precision instrument specified at 0.25% full scale to ISA S51.1, available with four electrical terminations.

TD6000 Electro Pneumatic Transducer
The problem

What Goes Wrong

Two different problems turn up on the same plant. One is mounting: an instrument has to go into a rack this week, a manifold next week and a classified area after that. The other is accuracy: a loop has been specified on a stated full-scale figure and a 1% linearity force balance unit will not satisfy it.

The answer

How This Range Solves It

The T6000 answers the first. Its modular construction permits any basic unit to be used explosion-proof, rack, wall, pipe, panel, DIN rail or in 3, 5, 10 or 15 unit manifolds, with six input and six output ranges on the catalog number. The T7800 answers the second, with a piezoelectric ceramic actuator, internal electronic feedback, 0.02% deadband and no measurable position or supply pressure effect.

Core strengths

Why Buyers Choose This Pattern

01

One unit, seven mounting configurations

The T6000 modular construction covers explosion-proof, rack, wall, pipe, panel, DIN rail and manifold installation.

02

Accuracy that goes in a specification

The T7800 is 0.25% full scale guaranteed and 0.15% typical to ISA S51.1, with 0.1% hysteresis and repeatability.

03

Four terminations on the T7800

TT terminal block, TA conduit pigtail, TD DIN 43650 and TR rear-terminal rack, in standard and extended range.

04

Interference and polarity protection

RFI and EMI effect below 0.5% of span, and no damage from reversed supply current or misapplication of up to 60 mA.

Who it suits

Who Orders From This Range

  • Rack rooms, marshalling panels and manifold blocks
  • Projects specified against CSA, ATEX or Factory Mutual approvals
  • Loops written around a stated ISA accuracy figure
  • Installations with vibration, outdoor exposure or nearby radio equipment
Industries

Where It Is Applied

All industry pages →

FAQ

Questions About The Fairchild Type Transducer Range

What is the difference between the T6000 and the T7800

The T6000 is the modular instrument built around mounting flexibility and a catalog number with six input and six output ranges. The T7800 is the precision instrument built around a piezoelectric actuator and internal electronic feedback, with published ISA accuracy figures.

What do the letters after T mean

They are the electrical connection. A is a 1/2 inch NPT conduit fitting with pigtail, D is DIN 43650, T is a terminal block, J is a junction box and R is rack mount.

Which are available in extended range

TT7800, TD7800 and TR7800 are catalogued in standard and extended range, and the TA7800 in extended range. In extended range units an additional relay section amplifies the output pressure.

Are these suitable for outdoor installation

The T7800 enclosure is NEMA 4X, Type 4 and IP65 rated for indoor and outdoor installations, and carries Canadian Registration Numbers certification for all territories and provinces.

Next step

Get A Part Number For Your Fairchild Loop

Send the nameplate data and the actuator spring range and the matching configuration comes back with a price and a lead time.