Selecting Creepage For The Pollution At Your Site at the Risheng plant

Selecting Creepage For The Pollution At Your Site

Almost every repeat flashover we are asked about comes back to the same thing: creepage was chosen from the system voltage and nothing else. Voltage tells you the minimum. The air at the site tells you what it actually needs.

Step by step

Every Stage And What Can Go Wrong At It

Site Assessment

Pollution severity is often described as light or heavy with nothing measurable behind it.

Describe the location concretely: distance from the coast, nearby cement, steel or chemical plants, agricultural spraying, desert dust, and how often washing is actually possible.

Total Versus Protected Creepage

Two insulators with the same total creepage can behave very differently in service.

We publish both figures where the data exists. The P-33-Y gives 900mm total with 450mm protected under the sheds, while the QS11405 gives 599mm total but only 200mm protected. Where rain washing is unreliable, the protected figure is the one that matters.

Envelope Constraints

The obvious fix, a bigger insulator, often will not fit the terminal board or the crossarm.

Several ranges offer more creepage inside a nearly unchanged envelope. The CD525 bushing adds 85mm of creepage over the 440mm version at almost the same body size.

Profile Selection

Dust that settles between washes bridges the leakage path regardless of how long it is.

Aerodynamic profile glass discs are shaped so wind carries deposits off the surface, which is why they are specified in desert and heavily polluted corridors.

Impulse Margin

Creepage solves pollution flashover but does nothing for lightning trips.

Impulse withstand is selected separately. The 24kV bushing at 150kV BIL, for example, sits above the 125kV usually quoted at that class, which suits overhead-fed networks.

Verification

A specification that cannot be checked on delivery is a specification in name only.

Creepage is verified against the drawing figure on routine inspection, and the tolerance band is published where one applies, such as 400mm plus or minus 10mm on the ShF-20G1.

Questions

Selecting Creepage For The Pollution At Your Site Questions

Why does my line keep flashing over when the insulator is rated for the voltage?
Because voltage sets the minimum creepage, not the required one. Salt, cement dust and industrial fallout form a conductive film on the surface, and the leakage current bridges a path that was adequate in clean air.
What is protected creepage?
The part of the leakage path that sits under the sheds where rain does not wash it. Where washing is unreliable it is a better predictor of behaviour than total creepage.
Can I get more creepage without changing my mounting?
Often yes. Send the installed part and the envelope you have to work within and we will tell you what fits.
Do aerodynamic profiles really reduce washing?
They are shaped so wind carries dust off the surface rather than letting it settle, which is why they are specified on dusty and arid line corridors.
What is the longest creepage you produce?
1015mm on the ANSI 57-14 line post and 935mm on the EN 36/250/P3 transformer bushing.

Selecting Creepage For The Pollution At Your Site

Send the drawing, sample or photographs and we will come back inside 24 hours with a pattern confirmation.