Solar pumping system
Solar pumping system is composed of a pv generator(solar panel), a pump and a solar pump inverter. Based on the desigh philosophy that it is more efficient to store water rather than electricity, there is no energy storing device such as storage battery in the system. The system is prepared to be combined with a elevated water storage, e.g. water tower or an uphill tank installation.
How to choose the solar panel
First, need to know the specific data sheet of the solar panel (power, Vmp,Voc)
Open Circuit Voltage (Voc)
Open circuit voltage is how many volts the solar panel outputs with no load on it.
This is a very important number, as it is the maximum voltage that the solar panel can produce under standard test conditions, so this is the number to use when determining how many solar panels you can wire in series going into your inverter or charge controller.
Maximum Power Point (Pmax)
The Pmax is the sweet spot of the solar panel power output, located at the “knee” of the curves in the graph above. It is where the combination of the volts and amps results in the highest wattage (Volts x Amps = Watts)
Maximum Power Point Current (Impp)
he Impp is the current (amps) when the power output is the greatest. It is the actual amperage you want to see when it is connected to the MPPT solar equipment under standard test conditions.
Maximum Power Point Voltage (Vmpp)
The Vmpp is the voltage when the power output is the greatest. It is the actual voltage you want to see when it is connected to the MPPT solar equipment (like an MPPT solar inverter) under standard test conditions.
When you use a Maximum Power Point Tracking MPPT) charge controller or inverter, this is the point that the MPPT electronics tries to keep the volts and amps at to maximize the power output. The wattage that a solar panel is listed as is the Pmax where Pmax = Vmpp x Impp
Second,select correct modes of solar pump inverter (voltage, power and current) as pumps nameplate and field requirement.
Get field requirement more in detail, such as water head, water flow, distance from pump to inverter, pumps voltage, pumps rated current, maximum current of pumps, and working conditions.
The selecting rated current of inveter must be equal or bigger than rated of using pump.
The bigger power of inverter should be selected for long distance from pumps to inverter. As experience, at least request 1.3 times bigger power input of solar arrays compare to rated power of pumps. It is also much related with the quality and efficiency of solar panels.
Input voltage, total power solar arrays selection
Input voltage, power solar arrays selection
Pumps model
Inverte models
Vmp
Voc
Total Power of solar arrays
110VAC pumps
1S
110*1.41=130VDC
156VDC
≧ (1.3 to 2.0) rated power of pumps
It is also depend on the quality of solar panels. The more power input, the better performance.
220VAC pumps
2S
220*1.41=310VDC
372VDC
380VAC pumps
4T (Max 800VDC)
380*1.41=540VDC
648VDC
480VAC pumps
4T ( Max 900VDC)
480*1.41=677VDC
812VDC
Although SG320 inverter built in high efficiency MPPT tracking arithmetic, up to 99.2% MPPT efficiency, but also need to consider many factors of solar radiation. It is no certain rules to determine exactly how many piece solar panels exactly input for system. If the output frequency can’t get to 50Hz/60Hz, consider to connect more solar panels.
Solar arrays selection table for inverter and pumps.
Take solar panels Voc38VDC, Vmp 31VDC, 265W. Check if enough DC voltage for system, Voc and Vmp. If the input is incorrect, the inverter will not work properly. If the output frequency is not high, lower than 50/60Hz even in good sunlight radiation, check if enough solar panels have been connected. The total power should be at least bigger 1.3 times than of rated power of pumps.
265w, 38Voc (Open circuit voltage), 31Vmp ( Voltage at Pmax)
Inverter models
Power of pump
Connection in series (PCS) (Vmp)
Connect in parallel ( Strings) Power
Total (PCS)
1S (110VAC)
0.75kw to 1.0kw
4 or 5 PCS
1* strings
5*1=5
2S (220VAC)
0.75kw to 1.5kw
10PCS
1* strings
10*1=10
2S (220VAC), Max 450vdc
2.2kw
11PCS
1* strings
11*1=11
4T(380VAC)
0.75kw to 2.2kw
18PCS
1* strings
18*1=18
4T(380VAC)
Max 900VDC
3.7kw
20PCS
1* strings
20*1=20
4T(380VAC)
5.5kw
18PCS
2* strings
18*2=36
4T(380VAC)
Max 900VDC
7.5kw
20pcs
2* strings
20*2=40
4T(380VAC)
11kw
18pcs
3* strings
18*3=54
4T(380VAC)
Max900VDC
15kw
20pcs
4* strings
20*4=80


Related Products

MPPT solar pump inverter for three phase AC and PMSM pumps, with dual DC and AC input.
View Product ›
SG320 solar pump drive with high MPPT efficiency, dry run protection and remote monitoring.
View Product ›
SG600 series MPPT solar pump inverter from 0.3 kW upwards with dual supply operation.
View Product ›
SG100 low start voltage solar pump inverter for small single phase and three phase pumps.
View Product ›Send the details of your own project and an engineer will tell you which model fits.