1000–4000 kVA

Shore Power Static Frequency Converter

Convert the quay into the voltage and frequency the ship is built for, at a published overall efficiency of ≥95% at full load.

Nepson shore power static frequency converter

Cold ironing without guessing the local grid

Frames are published at 1000, 1250, 1600, 2000, 3000 and 4000 kVA. Input frequency is 50 Hz ±10% or 60 Hz ±10%. Rated output frequency is 60 Hz or 50 Hz or 400 Hz at 0.01 accuracy. Input and output voltage levels are described as customizable.

Rectifier options: 6-pulse, 12-pulse or PWM. Input power factor is ≥0.90 / ≥0.96 / ≥0.99 respectively. Input current THD is ≤35% / ≤6% / ≤5% at rated load.

Published ratings

Frames1000 / 1250 / 1600 / 2000 / 3000 / 4000 kVA
Working environmentAmbient −10 °C to +45 °C; relative humidity 0–95%
ProtectionContainer type IP65; indoor type IP32
CoolingContainer: all air-conditioning cooling. Indoor: forced air cooling
AltitudeContinuous rated power below 1000 m; derate above 1000 m
Input systemIT or TN-C-S
Output systemIT (neutral insulation)
Output line current examples1000 kVA: 1312 A / 440 V. 4000 kVA: 5249 A / 440 V or 350 A / 6.6 kV
Voltage regulationStatic ≤0.5 V; dynamic ≤±1% (0–100% ladder load)
100% load stepSags/swells ≤±3%, recover in 0.5 base cycle, less than 8 ms
Output THDu≤1% (no load or linear load)
Imbalance / phase angleVoltage imbalance <1%; phase angle 120° ±0.1°
Efficiency≥95% at 100% rated load
Inverter devicesThree-phase full-bridge using Infineon PrimePACK IGBT or Semikron IPM