Nepson Industrial Co., Ltd · Shenzhen China · Since 2006
3 Phase Static Transfer Switch
Static Transfer Switch

3 Phase Static Transfer Switch

The STS is built with two independent power inlets. The load normally runs from the primary source. If the primary source fails, the secondary source picks the load up automatically and the transfer is...

Product Overview

What This Unit Does

The STS is built with two independent power inlets. The load normally runs from the primary source. If the primary source fails, the secondary source picks the load up automatically and the transfer is seamless to the connected equipment. Once the primary input is restored the switch returns the load to it. Standard ratings run from 63 A to 400 A per phase at 3 phase 380 V.

Key Benefits

  • Transfer time of 6 ms or less, short enough that servers and controllers do not reboot
  • Two separately independent sources give real redundancy, not a shared bus
  • Automatic return to the priority source removes a manual step after a fault
  • Efficiency of 98 percent or better keeps heat and running cost down
  • LCD shows voltage, current and power, LED shows working status at a glance

Problems It Solves

  • One feed fails and the whole rack drops out
  • Mechanical changeover gear is too slow and the load still sees an interruption
  • After a fault the load stays on the backup feed until somebody remembers to switch back

Application Scenarios

  • Dual feed server rooms and network closets
  • Redundant supply to PLC, DCS and instrument cabinets
  • Feeding a UPS bank from two utility transformers
  • Broadcast and telecom equipment rooms

Who It Is For

  • Data centre operators
  • Telecom and broadcast facilities
  • Plant electrical engineers
  • Building services contractors
Technical Features

How It Is Built

  • Two independent 3 phase inlets with source A as priority
  • SCR switching with first disconnect then connect sequencing
  • 3 pole transfer, optional 3 pole plus neutral
  • MCB or moulded case circuit breaker per rating
  • Air cooling with AC fans that start on over temperature
  • LCD metering of voltage, current and power
3 Phase Static Transfer Switch detail
Specifications

Published Data

Every figure below comes from the manufacturer data for this model family.

ModelsHPS-3363, HPS-33100, HPS-33160, HPS-33250, HPS-33300, HPS-33400
Input Phases3 phase
Input VoltageAC 380 V plus or minus 15 percent, other voltages customised
Input Frequency50 or 60 Hz
Output VoltageAC 380 V plus or minus 15 percent, 3 phase
Max Current Per Phase63 A, 100 A, 160 A, 250 A, 300 A, 400 A
ConnectorsTerminal block
BreakerMCB or moulded case circuit breaker
Transfer Time6 ms or less typical
Transfer Poles3P, optional 3P plus N
PriorityInput source A
Transfer TypeSCR, first disconnect then connect
Efficiency98 percent or better
CoolingAir cooling, AC fan starts on over temperature
Insulation ResistanceDC 500 V, 20 megohm or more
Withstand VoltageAC 1800 V, 10 mA for 1 minute
Operating Temperature0 to 45 degrees C
Relative Humidity0 to 99 percent non condensing
Operating Altitude1500 m or less
Dimensions600 x 600 x 1000 mm or 600 x 800 x 1760 mm depending on rating
Net Weight65, 70, 80, 105, 155 and 215 kg by rating
Manufacturing Process

From Cabinet To Tested Unit

Sheet metal cabinet build
SCR power assembly and busbar work
Control and metering wiring
Transfer timing test on both sources

Quality Control

  • Insulation resistance measured at DC 500 V
  • Withstand voltage held at AC 1800 V for one minute
  • Transfer sequence exercised on both inlets before shipment

Certifications

  • CE
  • RoHS

Customisation Options

  • Input and output voltage other than 380 V on request
  • 3 pole plus neutral switching
  • Breaker type matched to the upstream protection on site
Comparison

Against The Alternatives

Mechanical automatic transfer switchA mechanical ATS takes tens or hundreds of milliseconds. The STS transfers in 6 ms or less, so IT loads ride through without a restart.
Adding a second UPSA second UPS duplicates batteries and service cost. The STS gives source redundancy ahead of the UPS at a fraction of the footprint.
Use Guide

Getting It Right On Site

  • Feed the two inlets from genuinely independent transformers or feeders
  • Keep source A as the priority feed so return transfer is predictable
  • Size the rating on the actual per phase current, not on the cabinet size
  • Keep the operating area below 45 degrees C and 1500 m altitude, or derate
FAQ

Questions Buyers Ask

Will my servers reboot during a transfer?

Typical transfer time is 6 ms or less, which is inside the ride through window of a normal switch mode power supply, so connected equipment keeps running.

Does it switch the neutral?

Standard transfer is 3 pole. A 3 pole plus neutral version is available as an option.

What is the largest model?

HPS-33400 at 400 A per phase, in a 600 x 800 x 1760 mm cabinet weighing 215 kg.

How much power does the switch itself consume?

Efficiency is 98 percent or better, so losses stay low and the cabinet is air cooled.

Related

Other Equipment Engineers Specify With It

HPA Programmable AC Power Source

HPA Programmable AC Power Source

The HPA series is a variable frequency AC power source that reproduces the voltage and frequency used in any country on a single bench. It delivers...

View Specifications
Shore Power Static Frequency Converter

Shore Power Static Frequency Converter

A static frequency converter sized for quayside shore connection, from 1000 kVA to 4000 kVA. It takes the local port supply and delivers a clean IT...

View Specifications

Get A Quotation For The 3 Phase Static Transfer Switch

Send the rating, voltage, frequency and site conditions. We will confirm the model number and the cabinet dimensions.