Converting Between 50 Hz And 60 Hz Without Derating The Load
Process Guide

Converting Between 50 Hz And 60 Hz Without Derating The Load

Running a 60 Hz machine on 50 Hz changes motor speed, magnetising current and cooling. Static conversion gives the machine the supply it was designed for.

What Changes When The Frequency Changes

Induction motor speed follows supply frequency. Transformer and motor magnetising current rises when frequency falls at the same voltage. Fans and pumps driven by those motors shift along their curves, so cooling and flow change with them.

Why Voltage And Frequency Travel Together

Keeping the voltage to frequency ratio constant is what protects the magnetic circuit. A converter that sets both, rather than a transformer that sets only voltage, is what makes an imported machine behave as designed.

Static Conversion In Practice

A static converter rectifies the incoming supply and rebuilds the output with an IGBT inverter stage under space vector PWM control. Frequency accuracy of 0.01 and stability within 0.01 percent from no load to full load come from that control loop rather than from rotating mass.

Shore Power Static Frequency Converter

Harmonics Are Part Of The Specification

The rectifier front end decides what the installation puts back into the grid. A 6 pulse rectifier gives input current THD of 35 percent or less, a 12 pulse rectifier 6 percent or less, and a PWM rectifier 5 percent or less at full load. Pick against the limit the utility or port authority imposes.

Bench Scale Conversion

For test and QA work the same problem appears at a few kVA instead of a few thousand. A programmable AC source covering 40 Hz to 499.9 Hz handles it on the bench.

HPA Programmable AC Power Source

Equipment In This Guide

Products Referenced Above

Shore Power Static Frequency Converter

Shore Power Static Frequency Converter

A static frequency converter sized for quayside shore connection, from 1000 kVA to 4000 kVA. It takes the local port supply and delivers a clean IT...

View Specifications
HPA Programmable AC Power Source

HPA Programmable AC Power Source

The HPA series is a variable frequency AC power source that reproduces the voltage and frequency used in any country on a single bench. It delivers...

View Specifications

Industries

FAQ

Questions Buyers Ask

Can I just use a transformer to run 60 Hz equipment on 50 Hz?

A transformer changes voltage only. The frequency the motor and magnetic circuit see is unchanged, so speed and magnetising current are still wrong.

How accurate is static frequency conversion?

Output frequency accuracy is 0.01 and frequency stability is within 0.01 percent across the load range.

Check Your Case With An Engineer

Send the numbers from your own site and we will tell you which model the guide points to.