MTS-100 Meter Test System
Function Features Specification Order Info Function Calibrate all kind of single/three phase electronic/inductive active and reactive energy meter Automatically or single-step manually test basic error, creeping, starting, standard deviation of single/three.
- Model
- MTS-100
- Product line
- Meter Test and Calibration
- Manufacturer
- Kongter Test & Measurement Co., Limited, Shenzhen, China
- Quality standard
- ISO 9001:2015
- Customisation
- Tailored configurations available on request
Send your application details straight to us on WhatsApp, WeChat or by email. We do not use enquiry forms.
Specification
Full Details for MTS-100
- Calibrate all kind of single/three phase electronic/inductive active and reactive energy meter
- Automatically or single-step manually test basic error, creeping, starting, standard deviation of single/three phase energy meter, save user-defined calibrating scheme in Auto calibration
- Support variables influencetests, such as: Voltage, frequency, harmonics, reverse phase sequence, Voltage unbalance, etc
- Support special tests in energy meter type test, such as: phase triggering, pulse train triggering, etc
- Support DLT-645 communication protocol,multi-testing of multifunction meter such as: demand indication error, demand cycle error, time slot switching error, energy error of different tariff period, etc
- With OCXO, daily error of energy meter can be detected
- Output 2nd~63rd
- 8” TFT screen, interface friendly, easy to operate;
- Equipped with RS232, Ethernet, and WiFi interface,MTS-100 can either support stand-alone operation, PC control or handy wireless terminal control;
- Communicate with tested meters thru RS-485;
- Automatically calculate the error of meter, and the related data can be downloaded thru U-disk;
- Self-protection, alarming and displaying overload location for equipment output overload, Voltage short-circuit, Current open-circuit;
- Automatically detect, diagnose and alarm for failure.
- Remotely updating online, easily achieve software updating;
- Support calibration by user locally.
AC Voltage output:
Range: 100V, 220V, 380V
Adjusting range: (0~120) %RG, RG refers to range
Adjusting resolution: 0.01%RG, 0.1%RG, 1%RG, or 10% RG
Stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
Distortion: ≤0.2% (Non capacitive load)
Max output load: 20VA each phase
Accuracy: 0.05%RG (Class 0.05), 0.1%RG (Class 0.1)
AC Current output:
Range: 0.05A, 0.2A, 1A, 5A, 20A, 100A
Adjusting range: (0~120) %RG, RG refers to range, similarly hereafter
Adjusting resolution: 0.01%RG, 0.1%RG, 1%RG, or 10% RG
Stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
Distortion: ≤0.2% (Non capacitive load)
Max output load: 120VA (100A range)
Accuracy: 0.05%RG (Class 0.05); 0.1%RG (Class 0.1)
Power output
Power output stability: 0.01%/2min (Class 0.05), 0.02%/2min (Class 0.1)
Active/reactive power measurement accuracy: 0.05%RG;
Phase output
Output adjusting range: 0°~360°
Output adjusting resolution: 10°, 1°, 0.1°, or 0.01°
Resolution: 0.01°
Measurement accuracy: 0.05°
Power factor output:
Adjusting range: -1 ~ 0 ~ +1
Measuring resolution: 0.0001
Measurement accuracy: 0.0005
Frequency output
Adjusting range: 40Hz ~70Hz
Output adjusting resolution: 1Hz, 0.1Hz, 0.01Hz, or 0.001Hz
Resolution: 0.001Hz
Accuracy: 0.002 Hz.
Harmonic setting
Harmonic order: 2nd ~63rd
Harmonic amplitude: 0~40%
Harmonic angle: 0°~359.99°
Harmonic set error: 2~31times: ≤±0.1%, 32~63 times: ≤±0.2%;
Energy error measurement:
Active energy basic error limit:
±0.05%RD (Voltage 15V~660V, Current 0.02A~120A, PF≥0.5)
±0.1%RD (Voltage 15V~660V, Current 0.01A~0.02A, PF=1)
Reactive energy basic error limit:
±0.1%RD (Voltage 15V~660V, Current 0.02A~120A, PF≥0.5);
±0.2%RD (Voltage 15V~660V, Current 0.01A~0.02A, PF=1);
Energy pulse input
Input pulse: 3 channels active, 3 channels reactive
Other parameters:
Power supply: 90-265VAC/DC
Power frequency: 50Hz~60Hz
Power consumption: 50VA~1000VA
Environment condition: 20℃~30℃,Humidity: RH≤85%
Storage environment: -20℃~50℃
Size: 600mm(L)× 440mm(W)× 266mm(H)
Weight: 35kg
MTS-100 contains 2 models with different accuracy below:
MTS-100C: Accuracy Class 0.05
MTS-100B: Accuracy Class 0.1
Customers also viewed:
MTS-122 Meter Test System
MTS-50 Meter Test System
SPS-331 AC & DC Power SourceFAQ
Questions About This Model
Is this model certified
All Kongter products are strictly accredited by the international quality standard ISO 9001:2015.
Can this be customised for my application
Yes. Customised configurations are part of the standard offering. Tell us the system voltage, capacity or load you need to cover.
What is the lead time
Lead time depends on the configuration. Message us on WhatsApp at +86 135 1009 2292 or email [email protected] with your requirement and we will confirm it.
Do you provide training and support
Yes. Kongter's R&D team develops equipment aimed at field use, and product support is part of the offering. See the support pages for what is covered.
How do I get a quotation
Message us on WhatsApp or WeChat at +86 135 1009 2292, email [email protected], or call +86-755-2691 6832.
Related Models
More From Meter Test and Calibration








Request a Quote
Ask for a Price on MTS-100
Tell us the system you need to test and the quantity. We reply with a quotation and lead time.