Why A Current Transformer Secondary Must Not Stay Open
What happens if the secondary is open
A current transformer drives a current proportional to the primary through a low-impedance burden. If that secondary circuit is opened while the primary is energised, the core is driven toward saturation and a high voltage appears on the open secondary. That voltage can break insulation and is unsafe for anyone working on the terminal.
How to check before you isolate a meter
Short the secondary terminals or close the test-block shorting link before you remove a meter or relay. Restore the burden before you take the short off. Split-core CTs used on live cables follow the same rule — close the core and land the leads before you leave the feeder.

SCT Split Core Current Transformer
SCT Split Core Current Transformer is an AIRUIFA current transformer for panel builders and instrument OEMs that need a production CT they c

PR 5P20 Protection CT
PR 5P20 Protection CT is an AIRUIFA current transformer for panel builders and instrument OEMs that need a production CT they can label and
Questions Buyers Ask
Can I leave a spare CT unused on a live busbar?
Only if the secondary is shorted or connected to a burden. Do not leave the secondary open.